2026, 02, v.41 141-152
一种改进的星型CHB STATCOM相间均压策略
基金项目(Foundation): 国家自然科学基金资助项目(U21A20146)
邮箱(Email):
DOI:
投稿时间: 2026-03-02
投稿日期(年): 2026
修回时间: 2026-03-27
终审时间: 2026-04-02
终审日期(年): 2026
审稿周期(年): 1
发布时间: 2026-06-15
出版时间: 2026-06-15
移动端阅读
摘要:

针对星型级联H桥静止同步补偿器(Cascade H-bridge Static Synchronous Compensator, CHB STATCOM)在电网电压不对称跌落时存在的直流侧电压失衡及传统PI控制动态响应迟缓、抗干扰能力不足的问题,本文提出了一种基于滑模控制与零序电压注入相结合的改进型相间均压策略。研究通过引入零序电压处理方法,在dq坐标系下建立了能够精确解耦正、负序分量的数学模型,深入揭示了电压跌落导致相间有功功率不均衡的作用机理。设计具备动态鲁棒性的滑模电压控制器,通过切换超平面函数实时监测电压误差及其变化率,替代传统PI控制环节,以提升暂态过程的鲁棒性与动态响应速率。将滑模控制器输出的等效控制量转化为零序电压修正项,并与基于电网电压不平衡量计算所得的前馈零序电压分量相叠加,实现相间功率的精确再分配。利用380 V/7.5 kvar星型级联H桥静止同步补偿器仿真模型进行验证。结果表明,在电网电压发生不对称跌落的极端工况下,所提策略能够在120 ms内实现三相直流电压重新均衡,稳态误差控制在±2.5%以内,动态响应速度较传统PI控制提升约40%~50%,有效兼顾了稳态精度与动态性能,为提升星型CHB STATCOM在复杂电网故障条件下的运行稳定性提供了有效的技术途径。

Abstract:

To address the issues of DC-side voltage imbalance, sluggish dynamic response, and insufficient anti-interference capability of traditional PI control in star-connected cascaded H-bridge static synchronous compensators(CHB STATCOM) during asymmetric grid voltage sags, this paper proposes an improved phase-to-phase voltage equalization strategy combining sliding mode control(SMC) and zero-sequence voltage injection.First, a mathematical model capable of accurately decoupling positive-and negative-sequence components in the dq coordinate system is established by introducing a zero-sequence voltage processing method. This model deeply reveals the mechanism by which voltage sags lead to unbalanced active power between phases. Second, a dynamically robust sliding mode voltage controller is designed using a switching hyperplane function to monitor voltage errors and their rates of change in real-time. By replacing the traditional PI control, this approach significantly enhances the system′s robustness and dynamic response speed during transient processes. Furthermore, the equivalent output of the sliding mode controller is converted into a zero-sequence voltage correction term. This term is then integrated with the feedforward zero-sequence voltage component-calculated directly from the grid voltage imbalance-to achieve precise redistribution of inter-phase active power. Finally, a 380 V/7.5 kvar star-connected CHB STATCOM simulation model was developed for validation. The results demonstrate that under extreme asymmetric voltage sag conditions, the proposed strategy achieves three-phase DC voltage re-balancing within 120 ms, with steady-state errors maintained within ±2.5%. Compared with traditional PI control, the dynamic response speed is improved by approximately 40%~50%. This strategy effectively balances steady-state accuracy and dynamic performance, providing a robust technical solution for enhancing the operational stability of star-connected CHB STATCOMs under complex grid fault conditions.

参考文献

[ 1 ] Liao C,Liu Z,Wang H,et al.Small-signal model-based stability analysis for single-phase cascaded H-bridge STATCOM considering time delay[J].International Journal of Electrical Power & Energy Systems,2024,157:109880.

[ 2 ] Marzo I,Barrena J A,Sanchez-Ruiz A,et al.Reactive power limits of cascaded H-bridge STATCOMs in star and delta configuration under negative-sequence current withstanding[J].International Journal of Electrical Power & Energy Systems,2022,142:108267.

[ 3 ] Tan L,Zhang C,He B,et al.Comparative analysis of cascaded H-bridge STATCOM modulator harmonics for grid resonance suppression in Tokamaks[C]// 2025 International Conference on New Power System Technology (PowerCon),Hefei,China,2025:1-6.

[ 4 ] Sadeque F,Mohiuddin S M,Du W,et al.Per-phase control for chb converters with negative-sequence current and DC Voltage Balancing Control[C]// 2025 57th North American Power Symposium (NAPS),Storrs,CT,USA,2025:1-6.

[ 5 ] Xu J,He G,Tang S,et al.The unbalanced control research of fractional-order cascaded H-Bridge multilevel STATCOM[J].Fractal and Fractional,2025,9(1):30.

[ 6 ] Zhu X,Liang X,Gong K,et al.Negative sequence control for DC voltage balancing in three-phase cascaded H-bridge rectifiers considering DC-port failures[J].Journal of Power Electronics,2022,22(12):2025-2038.

[ 7 ] Liang H,Song H L,Xiu L C,et al.Coordination control of positive and negative sequence voltages of cascaded H-bridge STATCOM operating under imbalanced grid voltage[J].The Journal of Engineering,2019,2019(16):2743-2747.

[ 8 ] Ramos E R,Leyva R,Farivar G G,et al.Negative-sequence current capability in low-capacitance cascaded H-bridge static compensators with optimal third-harmonic circulating current injection[J].IEEE Transactions on Power Electronics,2022,38(4):4544-4558.

[ 9 ] Yang Z,Mei C,Cheng S,et al.Comparison of impedance model and amplitude-phase model for power-electronics-based power system[J].IEEE Journal of Emerging and Selected Topics in Power Electronics,2019,8(3):2546-2558.

[10] Kim Y,Cui S,Jung J J.A zero-sequence current-based clusterenergy balancing control in single-star multilevel converter with zigzag transformer[J].IEEE Access,2025,13:137665-137683.

[11] Jiang S,Li Q,Li H,et al.Split-phase power regulation of the three-phase voltage source converter via negative-sequence current injection[C]// 2025 9th International Conference on Power Energy Systems and Applications (ICoPESA),Nanjing,China,2025:239-244.

[12] Hu K,Zhao G,Lu D,et al.Simplified cluster voltage balamcing control based on zero-sequence voltage injection for star-connected cascaded H-bridge STATCOM[J].CSEE Journal Power and Energy Systems,2022,10(5):2255-2264.

[13] 刘宝稳,崔露瑶,曾祥君,等.配电网两相接地零序电压空间轨迹区域特征与故障相识别[J].电网技术,2026,50:2168-2180.

[14] Kim J M,Song G S,Jung J J.Zero-sequence voltage injection method for DC capacitor voltage balancing of wye-connected CHB converter under unbalanced grid and load conditions[J].Energies,2021,14(4):1019.

[15] Yarlagadda S R,Pathak M K.Azero sequence voltage injection method for cascaded H-bridge D-STATCOM[J].Journal of Power Electronics,2017,17(4):1088-1096.

[16] Yu Y,Konstantinou G,Townsend C D,et al.Comparison of zero-sequence injection methods in cascaded H-bridge multilevel converters for large-scale photovoltaic integration[J].IET Renewable Power Generation,2017,11(5):603-613.

[17] Lingom P M,Song-Manguelle J,Nyobe-Yome J M,et al.A comprehensive review of compensation control techniques suitable for cascaded H-bridge multilevel inverter operation with unequal DC sources or faulty cells[J].Energies,2024,17(3):722.

[18] Behrouzian E,Bongiorno M.Investigation of negative-sequence injection capability of cascaded H-bridge converters in star and delta configuration[J].IEEE Transactions on Power Electronics,2016,32(2):1675-1683.

[19] Ray S,Gupta N,Gupta R A.A comprehensive review on cascaded H-bridge inverter-based large-scale grid-connected photovoltaic[J].IETE Technical Review,2017,34(5):463-477.

[20] Chen H C,Cheng P T.A DC bus voltage balancing technique for the cascaded H-bridgeSTATCOM with improved reliability under grid faults[J].IEEE transactions on Industry Applications,2016,53(2):1263-1270.

[21] Wen N,Sun H,Zhang Z C,et al.Research on STATCOM control strategy of Cascaded H-bridge considering unbalanced conditions[C]// Journal of Physics:Conference Series,Hangzhou,China,2022,2338(1):012083.

[22] Aguilera R P,Acuna P,Yu Y,et al.Predictive control of cascaded H-bridge converters under unbalanced power generation[J].IEEE Transactions on Industrial Electronics,2016,64(1):4-13.

[23] 叶宗彬,葛程科,邓先明.级联H桥SVG直流侧电压均衡控制策略[J].实验室研究与探索,2023,42 (2):52-56+102.

基本信息:

中图分类号:TM761.12

引用信息:

[1]吴甜甜,高文根.一种改进的星型CHB STATCOM相间均压策略[J].山东师范大学学报(自然科学版),2026,41(02):141-152.